Model | Indoor Unit | FHA140BVMA | ||
Outdoor Unit | RZF140CVM | |||
Power supply | 1Ph/220/60hz | |||
Cooling Capacity (Min – Max) | kW | 14(6.2-15.5) | ||
Btu/hr | 47800 (21200-52900) | |||
Power consumption | Cooling | kW | 5.4 | |
COP | W/W | 2.59 | ||
CSPF | Wh/Wh | 4.78 | ||
Indoor Unit | Airflow rate (H / HM/ M/ ML/ L) | m3/min | 34/31.5/29/26.5/24 | |
Sound pressure level (H/ HM/ M/ ML /L) | dB(A) | 46/44/42/40/38 | ||
Dimensions (HxWxD) | mm | 235x1590x690 | ||
Machine weight | kg | 38 | ||
Certified Operation Range | CWB | 14 to 25 | ||
Outdoor Unit | Coil | Type | Micro Channel | |
Compressor | Type | Hermetically sealed swing type | ||
Motor Output | 2.4 | |||
Refrigerant Charge (R32) | 1.9 (Charged for 30m) | |||
Sound Pressure level | Cooling | 54 | ||
Night Quiet Mode | 45 | |||
Dimensions (HxWxD) | mm | 990x940x320 | ||
Machine Weight | kg | 64 | ||
Certified Operation range | CDB | 21 to 46 | ||
Piping connections | Liquid (Flare) | mm | 9.5 | |
Gas (Flare) | mm | 15.9 | ||
Drain | Indoor Unit | mm | VP20(I.D. 20 x O.D. 26) | |
Outdoor Unit | mm | 26 | ||
Max interunit piping length | m | 50 (Equivalent length 70) | ||
Max installation level difference | m | 30 | ||
Heat Insulation | Both liquid and gas piping |